The unit is designed to fit seamlessly into the ceiling space, providing a clean and modern look
1-way cassette
Key features:
  • Modern, thin and linear design panel
  • Automatic opening and closing of air discharge and air intake louvres
  • 3D ventilation
  • DC inverter fan motor
  • 5 fan speeds selectable with wired controller MIR-RS01
  • Quiet and thin
  • Standard intake filter
  • Standard condensate drain pump
Рowerful cooling
Рowerful cooling

Use the powerful cooling function to quickly reach the optimum temperature level when you first turn on the unit. This function will operate for a maximum of 15
minutes then the unit will return to a normal operation mode.

Individual valve control
Individual valve control

Independent control of horizontal and vertical vanes allows you to set the direction of air flow that will not disturb your comfort. And the wide opening angle of horizontal vane in heating mode ensures uniform temperature distribution across height.

Specifications Units MIBA-05X1EV1AD MIBA-07X1EV1AD MIBA-09X1EV1AD MIBA-12X1EV1AD
Capacity
Cooling kW 1,50 2,20 2,80 3,60
Heating kW 1,70 2,50 3,20 4,00
Electrical Parameters
Power supply Ph/V/Hz 1/220-230/50/(60) 1/220-230/50/(60) 1/220-230/50/(60) 1/220-230/50/(60)
Ventilation
Air flow (H/M/L) m3/h 530/490/450 530/490/450 530/490/450 550/530/490
Sound pressure
(H/M/L)
dB(A) 32/29/24 32/29/24 32/29/24 34/30/25
Sound power
(H/M/L)
dB(A) 46/43/38 46/43/38 46/43/38 48/44/39
Installation – Dimensions
Unit Dimensions
WxDxH
mm 875x505x185 875x505x185 875x505x185 875x505x185
Packaged unit
dimensions WxDxH
mm 1028x581x270 1028x581x270 1028x581x270 1028x581x270
Net weight / Gross
weight
Kg 15,3/17,9 15,3/17,9 15,3/17,9 15,3/17,9
Ø Liquid side
refrigerant pipe
mm (inch) 6,35 (1/4) 6,35 (1/4) 6,35 (1/4) 6,35 (1/4)
Ø Gas side
refrigerant pipe
mm (inch) 9,52 (3/8) 9,52 (3/8) 9,52 (3/8) 12,70 (1/2)
Panel
Model   M1B-1050IB M1B-1050IB M1B-1050IB M1B-1050IB
Panel Net dimensions
(WxDxH)
mm 1050x550x125 1050x550x125 1050x550x125 1050x550x125
Panel Packaging dimensions
(WxDxH)
mm 1133x623x197 1133x623x197 1133x623x197 1133x623x197
Panel Net/gross
weight
Kg 5,3/8,3 5,3/8,3 5,3/8,3 5,3/8,3

 

 

Specifications Units MIBA-16X2EV1AD MIBA-18X2EV1AD MIBA-24X2EV1AD
Cooling kW 4.5 5.6 7.1
Heating kW 5 6.3 8
Electrical Parameters
Power supply Ph/V/Hz 1/220-230/50/(60) 1/220-230/50/(60) 1/220-230/50/(60)
Ventilation
Air flow (H/M/L) m3/h 700/530/410 820/660/510 870/690/510
Sound pressure
(H/M/L)
dB(A) 41/36/32 40/36/32 42/36/32
Sound power
(H/M/L)
dB(A) 54/50/46 54/50/46 56/50/46
Installation – Dimensions
Unit Dimensions
WxDxH
mm 850x540x185 1170x540x185 1170x540x185
Packaged unit
dimensions WxDxH
mm 1043x648x270 1363x648x270 1363x648x270
Net weight / Gross
weight
Kg 21.3/25.5 26.0/31.4 27.1/32.5
Ø Liquid side
refrigerant pipe
mm (inch) 6,35 (1/4) 6,35 (1/4) 9,52 (3/8)
Ø Gas side
refrigerant pipe
mm (inch) 12.7 12.7 15.88
Panel
Model   M1B-1028IB M1B-1348IB M1B-1348IB
Panel Net dimensions
(WxDxH)
mm 1028x600x45 1348x600x45 1348x600x45
Panel Packaging dimensions
(WxDxH)
mm 1143x688x170 1463x688x170 1463x688x170
Panel Net/gross
weight
Kg 3.9/8.0 5.1/9.8 5.1/9.8
Dimensions