Ventilation
Fan coil unit MCFF is designed to maintain a comfortable indoor environment. The unit offers a wide range of air cooling and heating capacities for various applications.
Specifications | Units | MCFF-018 | MCFF-027 | MCFF-036 | MCFF-045 | MCFF-054 | |
Air flow rate, high / medium / low. | m3/h | 340/255/170 | 510/382/255 | 680/510/340 | 850/638/425 | 1020/765/510 | |
Cooling capacity, high / medium / low. | W | 1800/1440/1170 | 2700/2160/1755 | 3600/2880/2340 | 4500/3600/2925 | 5400/4320/3510 | |
Heating capacity, high / medium / low. | W | 2700/2160/1755 | 4050/3240/2633 | 5400/4320/3510 | 6750/5400/4388 | 8100/6480/5265 | |
Noise level | dB(A) | 42 | 44 | 46 | 47 | 49 | |
Water flow | m3/h | 0,39 | 0,55 | 0,7 | 0,82 | 0,91 | |
Drop in water pressure | Pa | 12 | 16 | 20 | 23 | 26 | |
Number of fans | 1 | 2 | 2 | 2 | 2 | ||
Fan motor | Number of engines | 1 | 1 | 1 | 1 | 1 | |
Input power | W | 49 | 66 | 84 | 100 | 118 | |
Maximum working pressure | MPa | 1,6 | 1,6 | 1,6 | 1,6 | 1,6 | |
Inlet / outlet water pipe | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) | ||
Drain pipe | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) |
Specifications | Units | MCFF-072 | MCFF-090 | MCFF-108 | MCFF-126 | |
Air flow rate, high / medium / low. | m3/h | 1360/1020/680 | 1700/1275/850 | 2040/1530/1020 | 2380/1785/1190 | |
Cooling capacity, high / medium / low. | W | 7200/5760/4680 | 9000/7200/5850 | 10800/8640/7020 | 12600/10800/8190 | |
Heating capacity, high / medium / low. | W | 10800/8640/7020 | 13500/10800/8775 | 16200/12960/10530 | 18900/15120/12285 | |
Noise level | dB(A) | 50 | 52 | 54 | 56 | |
Water flow | m3/h | 1,34 | 1,59 | 1,8 | 2,07 | |
Drop in water pressure | Pa | 28 | 32 | 38 | 42 | |
Number of fans | 3 | 4 | 4 | 4 | ||
Fan motor | Number of engines | 1 | 1 | 1 | 1 | |
Input power | W | 174 | 210 | 250 | 300 | |
Maximum working pressure | MPa | 1,6 | 1,6 | 1,6 | 1,6 | |
Inlet / outlet water pipe | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) | ||
Drain pipe | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) | Ø3/4" (DN20) |
Note.
1. The cooling capacity was tested under the following conditions: inlet air temperature 27°C dry bulb / 19.5°C wet
bulb; inlet/outlet water temperature 7°C / 12°C.
2. The heat output was tested under the following conditions: inlet air temperature 21°C dry thermometer; inlet
water temperature 60/50°C.
3. The noise level was tested in a completely echo-free room.
4. These performance and flow rates are given at a static pressure of 30Pa.
Model | Units | MCFF-018 | MCFF-027 | MCFF-036 | MCFF-045 | MCFF-054 | MCFF-072 | MCFF-090 | MCFF-108 | MCFF-126 |
A | mm | 770 | 920 | 990 | 1140 | 1220 | 1430 | 1650 | 1870 | 2020 |
B | mm | 440 | 590 | 660 | 810 | 890 | 1100 | 1320 | 1540 | 1690 |